TM 5-3805-293-23-2
0031
Table 1. Implement Code (2200-00 TO 2954-14) Troubleshooting Procedures - Continued.
CDI FMI CODE
TEST OR INSPECTION
CORRECTIVE ACTION
2252-14 Machine Articula-
a. Linkage securely connected
Linkage Loose or Sensor Not
tion Angle Sensor #2 Special
to machine and to sensor.
Secure - Perform installation and
Instruction - Continued
adjustment procedure for articulation
angle position sensor 1 (left) (WP
0257).
Proceed to step 2.
b. Remove articulation angle
Sensor damaged - Replace
position sensor 1 (left) and
articulation angle position sensor 1
visually inspect sensor hous-
(left) (WP 0257).
ing, and harness connector
Proceed to step 2.
for damage (WP 0257).
c.
Linkage bent or damaged.
Linkage Bent or Damaged - Replace
articulation angle position sensor 1
(left) linkage and perform adjustment
(WP 0257).
Proceed to step 2.
Sensor and Linkage OK - Proceed to
Test Step 3.
2. Using MSD (WP 0006), select
2252-14 Code Active - Repeat
Implement 120M and verify 2252- troubleshooting from the beginning of
14 is active.
this diagnostic code.
2252-14 Code Not Active -
Troubleshooting complete.
Test Step 3. Check Sensor.
1. Verify articulation angle position
Articulation Angle Position Sensor
sensor 2 (right) is within specifica-
2 (Right) OK - Proceed to Test Step 3.
tions refer to Adjustment in WP
Articulation Angle Position Sensor
0257.
2 (Right) Needs Adjustment - Adjust
sensor as directed (WP 0257).
Proceed to step 2.
2. Using MSD (WP 0006), select
2252-14 Code Active - Repeat
Implement 120M and verify 2252- troubleshooting from the beginning of
14 is active.
this diagnostic code.
2252-14 Code Not Active -
Troubleshooting complete.
0031-153