Table 1. Cab Heating, Air Conditioning, and 12 Volt Power Inverter Troubleshooting Procedures - Continued.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
5. No Power From 12 Volt
2.
Disconnect cab lower wiring har-
Power Inverter Or +12
ness connector P-C3 (WP 0009,
Volt Auxiliary Port - Con-
Figure 34) from cab upper wiring
tinued
harness connector R-C1 (WP
0009, Figure 33) (WP 0265).
3. Turn battery disconnect switch
and ignition switch to the ON posi-
tion (TM 5-3805-293-10).
Voltage 18 to 26 Volts - Replace cab
voltage between harness connec-
upper wiring harness (WP 0265).
tor P-C3 (WP 0009, Figure 34)
Proceed to step 5.
terminal 13 and machine ground.
Voltage Less Than 18 Volts -
Voltage should be 18 to 26 volts.
Replace cab lower wiring harness
(WP 0266).
Proceed to step 5.
5. Operate machine until engine
reaches normal operating temper-
ature (TM 5-3805-293-10).
6. Turn HVAC blower to maximum
speed (TM 5-3805-293-10).
7. Turn temperature control to the
No Warm Air Exiting From Air Vents
warmest setting and verify warm
- Repeat troubleshooting from begin-
air exiting from air vents.
ning.
Warm Air From Air Vents - 12 volt
power inverter OK, Troubleshooting
complete.
Test Step 5. Test 12 Volt Power
Inverter Ignition Supply Circuit
1. Turn battery disconnect switch
and ignition switch to the ON posi-
tion (TM 5-3805-293-10).
2. Disconnect cab lower wiring har-
ness connector P-C3 (WP 0009,
Figure 34) from cab upper wiring
harness connector R-C1 (WP
0009, Figure 33) (WP 0265).
0022-48